Dolphin Clip Black / Blue
Qty: 4Cable USB-A - USB-MiniB
Qty: 1Lead Set Voltage for Fluke 1735 and 1745
Qty: 1Battery Rechargeable Nickel-Metal Hydride 7.2 V 20 W
Qty: 1Clip Set
Qty: 2Case Soft
Qty: 1Current Probe Set, 3000A, 24 in
Qty: 1Battery Charger
Qty: 1USB Drive with Software and Manuals
Qty: 1Content is AI-generated. Verify critical details with manufacturer-provided resources.
The Fluke 1735 can log power parameters for up to 45 days continuously with its 3.5 MB internal memory capacity. The unit measures and records the most common three-phase power parameters including rms voltage, rms current, phase angle, voltage events, voltage and current THD, harmonics up to the 50th, active power, reactive power, power factor, active energy, and reactive energy over extended periods.
The Fluke 1735 includes four flexible current probes (Flexi Set) that are easily adjustable to three ranges: 15 A, 150 A, or 3000 A. This variable range capability provides high accuracy across nearly any application, from small circuits to large three-phase distribution systems. The instrument automatically detects, scales, and powers the probes when connected with a single plug.
The Fluke 1735 measures voltage and current harmonics up to the 50th harmonic with IEC 61000-4-7:2002 Class II accuracy. The unit measures individual harmonic components (Vm, Im) as well as total harmonic distortion for both voltage (THDV) and current (THDI). These measurements help uncover harmonic issues that can damage or disrupt critical equipment, with detailed accuracy specifications for different measurement ranges.
The Fluke 1735 provides voltage measurement accuracy of ±(0.2% of measured value + 5 digits) intrinsic error at reference conditions, with ±(0.5% of measured value + 10 digits) operating error across the full operating temperature range. The unit supports wye measurements from 57 V to 480 V ac and delta measurements from 100 V to 830 V ac with 0.1 V resolution.
The Fluke 1735 captures voltage dips, swells, and interruptions with 10 ms resolution using user-defined thresholds. This capability improves reliability by monitoring voltage events caused by load switching that can lead to spurious resets or nuisance circuit breaker tripping. The color screen provides instant confirmation of connections and displays captured events for on-screen analysis.
The Fluke 1735 operates for more than 12 hours with backlight set to low, or more than 6 hours with backlight set to high using the internal NiMH battery pack. The unit can also be powered by the included ac adapter (15 V to 20 V / 0.8 A) for continuous operation during extended logging sessions.
The Fluke 1735 is rated for IEC 61010-1 600 V CAT III applications with double or reinforced insulation and pollution degree 2. The main housing (excluding battery compartment) meets IP65 protection standards according to EN60529, making it suitable for rugged industrial environments. The unit is developed, designed, and manufactured according to DIN ISO 9001 quality standards.
Yes, the Fluke 1735 measures power factor with a range of 0.000 to 1.000 and resolution of 0.001 with ±1% of full scale accuracy. It also measures active energy (kWh), apparent energy (kVAh), and reactive energy (kVARh) with intrinsic error of ±(0.7% of measured value + frequency variation error + 15 digits). These measurements help quantify energy consumption for efficiency improvement assessments and justify energy-saving devices.